The coefficient of performance or COP (sometimes CP or CoP) of a heat pump, refrigerator or air conditioning system is a ratio of useful heating or cooling provided to work (energy) required. Higher COPs equate to higher efficiency, lower energy (power) consumption and thus lower operating costs. The COP is used in thermodynamics.

The COP usually exceeds 1, especially in heat pumps, because instead of just converting work to heat (which, if 100% efficient, would be a COP of 1), it pumps additional heat from a heat source to where the heat is required. Most air conditioners have a COP of 2.3 to 3.5. Less work is required to move heat than for conversion into heat, and because of this, heat pumps, air conditioners and refrigeration systems can have a coefficient of performance greater than one.

Coefficient of performance

For complete systems, COP calculations should include energy consumption of all power consuming auxiliaries. The COP is highly dependent on operating conditions, especially absolute temperature and relative temperature between sink and system, and is often graphed or averaged against expected conditions.

Coefficient of performance

Performance of absorption refrigerator chillers is typically much lower, as they are not heat pumps relying on compression, but instead rely on chemical reactions driven by heat.

Coefficient of performance

Equation

The equation is:

where

is the useful heat supplied or removed by the considered system (machine). is the net work put into the considered system in one cycle.

The COP for heating and cooling are different because the heat reservoir of interest is different. When one is interested in how well a machine cools, the COP is the ratio of the heat taken up from the cold reservoir to input work. However, for heating, the COP is the ratio of the magnitude of the heat given off to the hot reservoir (which is the heat taken up from the cold reservoir plus the input work) to the input work:

where

is the heat removed from the cold reservoir and added to the system; is the heat given off to the hot reservoir; it is lost by the system and therefore negative (see heat).

Note that the COP of a heat pump depends on its direction. The heat rejected to the hot sink is greater than the heat absorbed from the cold source, so the heating COP is greater by one than the cooling COP.

Theoretical performance limits

According to the first law of thermodynamics, after a full cycle of the process and thus . Since , we obtain

For a heat pump operating at maximum theoretical efficiency (i.e. Carnot efficiency), it can be shown that and thus where and are the thermodynamic temperatures of the hot and cold heat reservoirs, respectively.

At maximum theoretical efficiency, therefore

which is equal to the reciprocal of the thermal efficiency of an ideal heat engine, because a heat pump is a heat engine operating in reverse.

Similarly, the COP of a refrigerator or air conditioner operating at maximum theoretical efficiency,

applies to heat pumps and applies to air conditioners and refrigerators. Measured values for actual systems will always be significantly less than these theoretical maxima.

In Europe, the standard test conditions for ground source heat pump units use 308 K (35 °C; 95 °F) for and 273 K (0 °C; 32 °F) for . According to the above formula, the maximum theoretical COPs would be

Test results of the best systems are around 4.5. When measuring installed units over a whole season and accounting for the energy needed to pump water through the piping systems, seasonal COP's for heating are around 3.5 or less. This indicates room for further improvement.

The EU standard test conditions for an air source heat pump is at dry-bulb temperature of 20 °C (68 °F) for and 7 °C (44.6 °F) for . Given sub-zero European winter temperatures, real world heating performance is significantly poorer than such standard COP figures imply.