CAPACITY OF GENERATING STATIONS AND WEIGHT OF CONDUCTORS.
+---------------------------------+-----------+------------+------------+ | | Kilowatt |Total Weight| Pounds of | | |Capacity at| of | Conductors | | Location of Transmission. |Generators.|Conductors. |per Kilowatt| | | | | Capacity. | +---------------------------------+-----------+------------+------------+ |Wilbraham to Ludlow | 4,600 | 17,820 | 3.7[A] | |Sewall’s Falls to railroad shops | 50 | 6,914 | 15 | |Into Victor, Colo. | 1,600 | 15,960 | 10 | |To Dales, Ore. | 1,000 | 33,939 | 34 | |Apple River to St. Paul | 3,000 | 159,600 | 53 | |Farmington River to Hartford | 1,500 | 54,054 | 36 | |Cañon City to Cripple Creek | 1,500 | 59,079 | 39 | |Yadkin River to Salem | 1,500 | 58,073 | 39 | |Montmorency Falls to Quebec | 2,400 | 189,056 | 79 | |Cañon Ferry to Butte | 5,700 | 658,320 | 115 | |San Gabriel Cañon to Los Angeles | 1,200 | 73,002 | 61 | |Welland Canal to Hamilton | 6,000 | 376,494 | 63 | |Madrid to Bland, N. M. | 600 | 127,680 | 212 | |Ogden to Salt Lake City | 2,250 | 292,365 | 129 | |Santa Ana River to Los Angeles | 2,250 | 664,830 | 295 | |Colgate to Oakland | 11,250 | { 906,954 | 81 | | | | { 446,627 | 40[A] | +---------------------------------+-----------+------------+------------+ [A] Aluminum.
These wide variations in the volts per mile on transmission lines and in length of lines lead to different weights of conductors per kilowatt of generator capacity. All other factors remaining constant, the weight of conductors per kilowatt of generator capacity would be the same whatever the length of the transmission, provided that the volts per mile were uniform for all cases. One important factor, the percentage of loss for which the line conductors are designed at full load, is sure to vary in different cases, and lead to corresponding variations in the weights of conductors per kilowatt of generator capacity. In conductors of equal length one pound of aluminum has nearly the same electrical resistance as two pounds of copper, and this ratio must be allowed for when copper and aluminum lines are compared.
From the table it may be seen that the weight of conductors per kilowatt of generator capacity for the transmission from Santa Ana River is 29.5 times as great as the like weight for the line into Victor. But the volts per mile are four times as great on the Victor as they are on the Santa Ana River line. The extreme range of the cases presented is that between the Ludlow plant, with the equivalent of 7.4 pounds, and the Santa Ana River system with 295 pounds of copper conductors per kilowatt of generator capacity. Three transmissions with 1,575 to 2,555 volts per mile have the equivalent of 7.4 to 15 pounds of copper each, per kilowatt of generator capacity.