In America, a strong point is made of utilising, as far as possible, all the existing natural conductors that are to be found upon a building, such as gutters, rain-pipes, and other metal surfaces. During a tempest, the opposite electricities of the earth and the air often select, by their inductive influence, a rain-pipe, gutter, metal roof, &c., for the passage of an electric discharge between them, and unless these metallic surfaces are connected with the earth, they are apt to be dangerous. But if they are properly connected together, and provided with a good earth-contact, they materially assist to diminish the intensity of a discharge.

In the case of a building with a roof of slate, wood, or other material of low conductivity, a conductor made of either bar iron or stranded cable is placed along the ridge and gable ends, and carefully connected with the gutters and rain-pipes; where the rain-pipes are less than three inches in diameter, the bar or cable conductor is often extended from the roof down the side of the building, and connected with the earth terminal. When this is done, the bar or cable conductor is placed between the rain-pipe and the wall of the building, or at any rate close to the rain-pipe, and connected with it by solder or bolts.

Lightning Conductors — Part 88

All metallic chimney caps, cornices and railings on the tops of buildings, as well as the water-pipes, gas-pipes, hot water-pipes, and other large or long pieces of metal, whether they occur inside or outside the building, are connected with each other by a conductor composed of light stranded wires, each about three-sixteenths of an inch in diameter; they are also connected with the main conductor at its nearest point. Where several adjacent buildings have each a metallic roof, these roofs are connected together by means of a horizontal conductor.

Lightning Conductors — Part 88

The terminal rod of the conductor generally projects about four feet above the chimney or other highest point of the building. It consists of a round iron rod seven-sixteenths of an inch in diameter, the lower extremity being hammered out for the purpose of fastening it to the conductor by soldering and screws or by bolts. A small building, not exceeding twenty-five feet in length or breadth, is generally fitted with either one terminal rod placed on the centre of the ridge of the roof, or with two rods, one at each end of the ridge, the latter method being the preferable one. In larger buildings terminal rods are placed at intervals of about twenty feet along the roof. The upper end of the rod is sometimes pointed, but not always, the argument being that although the ordinary end of a rod is blunt when used in connection with a Leyden jar, but that when applied to a thunder-cloud, which extends over thousands of acres, it becomes pointed, and bears the same proportion to a thunder-cloud as the sharp point of a needle does to the hand of a man. Occasionally the point is tipped with platinum, gold, silver, or pure copper, in order to prevent oxidation, but this is not considered essential, it being presumed that, practically no amount of rust on the top would impair the efficacy of the terminal rod.

Lightning Conductors — Part 88