~Ques. What kind of current is generally used for the auxiliary circuit of a circuit closing relay?~

~Ques. Where is this current usually obtained?~

Hawkins Electrical Guide v. 7 (of 10) — Part 57

Ans. From a storage battery, or from the exciter.

Hawkins Electrical Guide v. 7 (of 10) — Part 57

~Ques. For what current are the contacts ordinarily designed?~

Hawkins Electrical Guide v. 7 (of 10) — Part 57

[Illustration: FIGS. 2,292 to 2,300.--General Electric alternating current, instantaneous overload ~circuit closing~ relays, covers removed. The function of a circuit closing relay is to close an electrical circuit, usually direct current, through a trip coil on an oil switch or circuit breaker, or it may short circuit a low voltage release coil, and thereby open the oil switch or circuit breaker on occurrence of the condition upon which the relay is designed to operate. Direct current at 125 or 250 volts taken from exciter bus bars or storage battery system is generally used for the tripping circuit. Circuit closing contacts have a cone shaped central element of carbon or metal which makes contact with flexible contact fingers symmetrically arranged above the cone. These contacts will make and break a circuit of 10 amperes at 125 volts without the use of auxiliary circuit opening switches. Relays are made with two or three contacts for connecting one side of a direct current circuit through one or two separate circuits, or trip coils respectively, to the side of opposite polarity. Usually only two contacts are required. Where two or more trip coils are used, which may not be connected permanently in parallel, the three contact relays are selected and in some cases four contacts furnished.]

~Primary and Secondary Relays.~--Primary relays are sometimes called series relays as they have the current coils connected directly in series with the line, both on high and low tension circuits.

Secondary relays receive their current supply from the secondary circuits of current transformers. Alternating current relays connected to secondary of pressure transformers and relays with both current and pressure windings are included in this class.

~Ques. What is the usual winding of the coils?~

Ans. The current coils are usually wound for 5 amperes and the pressure coils for 110 volts.

[Illustration: FIG. 2,301.--Alternating current low voltage circuit closing low voltage relay, for 600 volts or less. The contacts are similar to those of the circuit closing overload type except that they are inverted. As long as the pressure is normal the contact cone is held above the contacts. When the pressure falls below one half normal, the cone and plunger rod drop and close the contact. This relay does not pick up its own plunger. The plunger rod is pushed up by hand after the pressure circuit is established. Low voltage relays are generally used in connection with a low voltage release or shunt trip coil on an oil switch or a circuit breaker. They are used in connection with motor booster sets to prevent a disastrous speed of the booster which might result from the loss of alternating current power. They are also sometimes used for indicating purposes.]